Computational Fluid Dynamics Simulations to Assess Spatial Variability and Optimal Ventilation Scenarios for Biological Laboratory Exposures

Appl Biosaf. 2023 Dec 1;28(4):256-264. doi: 10.1089/apb.2023.0001. Epub 2023 Dec 5.

Abstract

Introduction: A significant amount of uncertainty exists regarding potential human exposure to laboratory biomaterials and organisms in Biosafety Level 2 (BSL-2) research laboratories. Computational fluid dynamics (CFD) modeling is proposed as a way to better understand potential impacts of different combinations of biomaterials, laboratory manipulations, and exposure routes on risks to laboratory workers.

Methods: In this study, we use CFD models to simulate airborne concentrations of contaminants in an actual BSL-2 laboratory under different configurations.

Results: Results show that ventilation configuration, sampling location, and contaminant source location can significantly impact airborne concentrations and exposures. Depending on the source location and airflow patterns, the transient and time-integrated concentrations varied by several orders of magnitude. Contaminant plumes from sources located near a return vent (or exhaust like a fume hood or ventilated biosafety cabinet) are likely to be more contained than sources that are further from the exhaust. Having a direct flow between the source and the exhaust (through-flow condition) may reduce potential exposures to individuals outside the air flow path.

Conclusion: Designing a BSL-2 room with ventilation and airflow patterns that maximize through-flow conditions to the return/exhaust vents and minimize dispersion and mixing throughout the room is, therefore, recommended. CFD simulations can also be used to assist in characterizing the impacts of supply and return vent locations, room layout, and source locations on spatial and temporal contaminant concentrations. In addition, proper placement of particle sensors can also be informed by CFD simulations to provide additional characterization and monitoring of potential exposures in BSL-2 facilities.

Keywords: BSL-2; airflow modeling; biosafety; computation fluid dynamic modeling; laboratory-acquired infections.